Electrical Rough-In | 7/14/2006 | 7/14/2006 | 7/14/2006 | P | PASS |
Mike Kinnear
|
|
|
eric - trench; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok cover under ground conduit to pool service
|
Conference | 7/13/2006 | 7/13/2006 | 7/13/2006 | | PASS |
Jim Schmer
|
|
|
|
Permanent Service | 7/12/2006 | 7/13/2006 | 7/13/2006 | A | PASS |
Jim Schmer
|
|
|
ERIC; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g rec - ok jms
|
Rough-In Permanent Service | 7/11/2006 | 7/12/2006 | 7/12/2006 | P | FAIL |
Mike Kinnear
|
|
|
rock - call 1/2 hr prior to insp -around 2pm if possible; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley service not ready correction nec 300.5 conduit depth for pvc 18 inches or more
|