Final | 10/9/2006 | 10/10/2006 | 10/10/2006 | A | PASS |
Bob Reichert
|
|
|
any questions please give James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford corr made, signed occ card, ok to final
|
Final | 9/21/2006 | 9/22/2006 | 9/22/2006 | P | PART |
Bob Reichert
|
|
|
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford part final ok, signed t/o card, left corr notice, nec 210.62 at least 1 recptacle shall be installed directly above a show window for each 12 linear feet or fraction thereof , 408.4 circuit directory shall be provided and specific as to its purpose, NOTE: corrections shall be made within 2 weeks or further action will be taken, such as removing power., wrote correction to builder/owner: nec 725.2 installed cl2,3,pltc cables not terminated at equipment and not identified for future use with a tag shall be removed per 725.3(B), Note,, correction shall be made within 2 weeks or further action will be taken, such as removing power
|
Final | 9/20/2006 | 9/21/2006 | 9/21/2006 | P | CANC |
Bob Reichert
|
|
|
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford
|
Final | 9/19/2006 | 9/20/2006 | 9/20/2006 | A | PART |
Bob Reichert
|
|
|
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford down stairs ok except floor boxes, no mezzanine access- need to check, need to check elev, told needed showroom recpts
|
Electrical Rough-In | 9/14/2006 | 9/15/2006 | 9/15/2006 | A | PART |
Bob Reichert
|
|
|
this is for a ceiling inspection, any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover 6 office clgs only, 1st fl, left corr notice about rest of fixtures, nec 400.8 flexible cord and cables shall not be used as a substitue for the fixed wiring of a structure, talked to contr
|
Electrical Rough-In | 9/11/2006 | 9/11/2006 | 9/11/2006 | P | PART |
Bob Reichert
|
|
|
ANY QUESTIONS PLEASE CALL JAMES LINGELBAUGH; Phone #: ###-#### Internet Inspection Request from: Jeff Radford cash wrap only ok to cover
|
Electrical Rough-In | 8/31/2006 | 8/31/2006 | 8/31/2006 | P | PASS |
William E Thomas
|
|
|
ANY QUESTIONS PLEASE CALL JAMES LINGELBAUGH; Phone #: ###-#### Internet Inspection Request from: Jeff Radford cloud cieling light ok to cover
|
Electrical Rough-In | 8/24/2006 | 8/25/2006 | 8/25/2006 | A | PART |
Bob Reichert
|
|
|
this is for the 1st floor, any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford mezzanine walls only ok to cover
|
Electrical Rough-In | 8/17/2006 | 8/18/2006 | 8/18/2006 | A | PART |
Bob Reichert
|
|
|
this for a final on the second floor temporary occupancy, any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford 2nd floor ok for t/o, signed card, left corr notice BCC need to see partitions and permanent lighting (pendants)
|
Electrical Rough-In | 8/17/2006 | 8/17/2006 | 8/17/2006 | P | NR |
Bob Reichert
|
|
|
this is for a temporary occupancy for the 2nd floor, any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford called contr, open ceiling, open elevator, construction going on, hard wired so cord, open switch plates, not ready for inspection, fee due
|
Electrical Rough-In | 8/16/2006 | 8/16/2006 | 8/16/2006 | P | PART |
Bob Reichert
|
|
|
this is for temporary occupancy on the 2nd floor any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover west 1/2 ceiling only, NOTE: main room lighting ok for now, but pendant fixtures need inspection once they replace temp fixtures
|
Electrical Rough-In | 8/14/2006 | 8/15/2006 | 8/15/2006 | A | PART |
Bob Reichert
|
|
|
THIS IS FOR A CEILING INSPECTION, ANY QUESTIONS PLEASE CALL JAMES LINGELBAUGH; Phone #: ###-#### Internet Inspection Request from: Jeff Radford east 1/2 ceiling 2nd floor ok to cover
|
Rough-In Permanent Service | 8/7/2006 | 8/8/2006 | 8/8/2006 | A | PASS |
Bob Reichert
|
|
|
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford stub wall 1st floor ric ok, p/s exst meter pak, n ok, 2 meters
|
Electrical Rough-In | 8/2/2006 | 8/2/2006 | 8/2/2006 | P | PART |
Bob Reichert
|
|
|
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford 1st fl walls except short ns wall ok to cover
|
Electrical Rough-In | 7/21/2006 | 7/21/2006 | 7/21/2006 | P | PASS |
Bob Reichert
|
|
|
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford 2nd floor walls only , 1st floor nw wall only ok to cover
|
Electrical Rough-In | 7/18/2006 | 7/19/2006 | 7/19/2006 | A | PART |
Bob Reichert
|
|
|
this is for a underground rough-in, any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover u/g 1st floor walker duct and perimeter walls 2nd floor
|
Electrical Rough-In | 7/14/2006 | 7/17/2006 | 7/17/2006 | A | PASS |
Bob Reichert
|
|
|
this is for pipe underground inspection, any questions please call james Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover u/g from wall to elev pit
|