Final | 10/11/2006 | 10/13/2006 | 10/13/2006 | A | FAIL |
Bob Reichert
|
|
|
toni; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice,fee due, corrections not done,nec 406.4(D) receptacle faces shall be flush or project from faceplates,404.9 faceplates shall seat against finished surface, 408.4 circuit directory shall be clear, concise, and cpmplete, 348.30 fmc shall be securely fastened within 12" of box, 725.8 cl1,2,3 cable shall be supported by building structure, 406.8(B) wet location recpt shall have weather-proof enclosure whether or not attachment plug cap is inserted,110.3(B) equipment shall be installed according to instructions,fan switch and cover, 110.12(C) there shall be no damaged receptacles
|
Final | 10/9/2006 | 10/11/2006 | 10/11/2006 | P | NH |
Bob Reichert
|
|
|
Work performed by Matthew White. Internet Inspection Request from: Matt Santacruz called contr, left card
|
Electrical Rough-In | 10/6/2006 | 10/9/2006 | 10/9/2006 | A | PASS |
Bob Reichert
|
|
|
Work performed by Matthew White.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz called contr about bkr label,faceplates, fan sw knob, loose recpt mbr, furnace room, ric ok, will call for final, need to add sticker for service, label bkr spare
|
Conference | 7/20/2006 | 7/20/2006 | 7/20/2006 | A | PART |
Pat Lass
|
|
|
matt - per pat; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley oked location of meter combo
|