Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE06-02718
StatusFinaled
Name S & M ELECTRIC
Site Address 11456 W GRANGER ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/18/200610/19/200610/19/2006APASS
DetailsBob Reichert
mike - note: call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
Electrical Rough-In7/25/20067/25/20067/25/2006PPASS
DetailsBob Reichert
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ric ok
Rough-In Permanent Service7/24/20067/25/20067/25/2006ACANC
DetailsBob Reichert
michael; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see p/s and also ri
Electrical Rough-In7/25/20067/25/20067/25/2006AFAIL
DetailsBob Reichert
michael; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left message, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.30 nm cable shall not be stapled on edge, 210.52 loft and storage room shall have recpts installed (6'-12'), BCC all make-up shall be done, address shall be posted
Permanent Service7/25/20067/25/20067/25/2006APASS
DetailsBob Reichert
michael; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok