Final | 10/18/2006 | 10/19/2006 | 10/19/2006 | A | PASS |
Bob Reichert
|
|
|
mike - note: call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
Electrical Rough-In | 7/25/2006 | 7/25/2006 | 7/25/2006 | P | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ric ok
|
Rough-In Permanent Service | 7/24/2006 | 7/25/2006 | 7/25/2006 | A | CANC |
Bob Reichert
|
|
|
michael; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see p/s and also ri
|
Electrical Rough-In | 7/25/2006 | 7/25/2006 | 7/25/2006 | A | FAIL |
Bob Reichert
|
|
|
michael; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left message, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.30 nm cable shall not be stapled on edge, 210.52 loft and storage room shall have recpts installed (6'-12'), BCC all make-up shall be done, address shall be posted
|
Permanent Service | 7/25/2006 | 7/25/2006 | 7/25/2006 | A | PASS |
Bob Reichert
|
|
|
michael; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
|