Final | 10/25/2006 | 10/26/2006 | 10/26/2006 | P | PASS |
Pat Lass
|
|
|
call for access\\Thane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Electrical Rough-In | 8/18/2006 | 8/18/2006 | 8/18/2006 | P | PASS |
Bob Reichert
|
|
|
thane; Phone #: ###-#### Note: please 1/2 hr prior to inspection after 4:00 Internet Inspection Request from: Cathy Chiles corr made, ric ok
|
Electrical Rough-In | 8/17/2006 | 8/17/2006 | 8/17/2006 | P | FAIL |
William E Thomas
|
|
|
thane - call 1/2hr prior to meet there; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley still needs stapling of nmc
|
Electrical Rough-In | 8/7/2006 | 8/7/2006 | 8/7/2006 | P | FAIL |
Bob Reichert
|
|
|
thane - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley met owner, corrections are:11/4" nm cable, ground metal boxes, box outside to be flush with finished surface, add recpt in bedroom wall, make-up to be done, support nm within 8" of box,provide afci for final, owner made notes for corrections
|
Conference | 7/27/2006 | 7/28/2006 | 7/28/2006 | A | DONE |
Bob Reichert
|
|
|
tom Note: please call 1/2 hr prior; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 336 did
|