Final | 12/11/2006 | 12/11/2006 | 12/11/2006 | P | FAIL |
Bob Reichert
|
|
|
Rich Note: Call 1/2 prior to insp ; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett met owner, nec 210.8(A)(2) garage recpts shall be gfci protected, 408.4 circuit directory shall be done, 312.5 abrasion protection shall be provided for conductors entering enclosures, 110.12(A) unused openings shall be closed in panel
|
Final | 9/5/2006 | 9/6/2006 | 9/6/2006 | A | CANC |
Mike Kinnear
|
|
|
richard; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley wrong type inspection
|
Electrical Rough-In | 9/6/2006 | 9/6/2006 | 9/6/2006 | A | PASS |
Mike Kinnear
|
|
|
richard; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok cover ri
|
Final | 9/1/2006 | 9/5/2006 | 9/5/2006 | A | NR |
Mike Kinnear
|
|
|
rich; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley need move outlets higher 24inch or more & just couple 1 1/4 stapling
|
Conference | 7/31/2006 | 7/31/2006 | 7/31/2006 | P | DONE |
Jack Frank
|
|
|
richard; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Conference | 7/28/2006 | 7/31/2006 | 7/31/2006 | A | NH |
Jack Frank
|
|
|
richard ###-#### owner was not there his wife will have him reschedule
|