Final | 8/9/2006 | 8/9/2006 | 8/9/2006 | P | PASS |
Bob Reichert
|
|
|
donna; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
|
Final | 8/7/2006 | 8/8/2006 | 8/8/2006 | A | FAIL |
Bob Reichert
|
|
|
adam ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called, left corr notice, nec 230.24(B)(4) minimum clearance from ground shall be 18' on other than residential property, 312.5 all conductors entering enclosures shall have abrasion protection, 230.28 mast shall be supported by guy kit, 250.53(G) ground rods shall be flush with or below ground level
|