Final | 9/6/2006 | 9/7/2006 | 9/7/2006 | A | PASS |
Bob Reichert
|
|
|
craig; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked to owner to put on recpt covers and nm cable shall not be stapled on edge, ok to final
|
Final | 9/5/2006 | 9/5/2006 | 9/5/2006 | P | FAIL |
Bob Reichert
|
|
|
craig ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice, nec 210.8(A)(2),(3) all receptacles on 15 or 20a circuits shall have gfci protection, 406.8(B) outside receptacles shall have weatherproof covers whether or not plug is inserted
|
Electrical Rough-In | 8/25/2006 | 8/25/2006 | 8/25/2006 | P | PASS |
Bob Reichert
|
|
|
Craig; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr made, ric ok
|
Electrical Rough-In | 8/23/2006 | 8/24/2006 | 8/24/2006 | A | FAIL |
Bob Reichert
|
|
|
craig; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt met owner, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.17(C) nm cable shall be secured within 8" of box, BCC all make-up shall be done-boxes set
|
Electrical Rough-In | 8/21/2006 | 8/21/2006 | 8/21/2006 | P | CANC |
Bob Reichert
|
|
|
craig - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, cust said to cancel till later
|
Electrical Rough-In | 8/8/2006 | 8/8/2006 | 8/8/2006 | P | PASS |
Bob Reichert
|
|
|
craig - buried cable; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g only house to garage
|