Electrical Rough-In | 8/25/2006 | 8/25/2006 | 8/25/2006 | P | FAIL |
Jack Frank
|
|
|
elmer; Phone #: ###-####/###-#### cell Internet Inspection Request from: Cathy Chiles corr. met owner 110.12(A) seal KOs replace pastic boxes with extra KOs broken out, 300.4 nail plates and 11/4", 230. 24(A) 8ft clearence over roof, 314.20 boxes shall be flush with siding outside fixture110.26 needs clearence for p/s, 314.43 no scfrews in plastic boxes, 330.40 use conn. listed for MC furnace,210.52or104(A)(1) grd or bond water 310.16 shall not use 14 on 20 amp circuit, note needs 2" rmc,or imc for mast, 3 way wiring all messed up wiring not ready partial corr. only told owner also makeup not done cow
|
Rough-In Permanent Service | 8/24/2006 | 8/25/2006 | 8/25/2006 | A | NH |
Jack Frank
|
|
|
elmer - as early as possible; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called left message notice posted
|