Final | 1/28/2007 | 1/29/2007 | 1/29/2007 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/28/2007 at 9:04:02 AM. Contact: ###-####. ok card signed
|
Final | 1/25/2007 | 1/26/2007 | 1/26/2007 | P | FAIL |
Jack Frank
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall on prior inspection tlked with contr about meyal raceway in nonmetallic enclosure 314.3 explained the requirements of NEC and manufactures instructions, violation not made no final
|
Final | 1/15/2007 | 1/16/2007 | 1/16/2007 | A | PART |
Jack Frank
|
|
|
This is for temp occupancy. Need final Phone #: ###-#### t/o ok
|
Final | 1/11/2007 | 1/12/2007 | 1/12/2007 | A | NR |
William E Thomas
|
|
|
daniel - note: final for temp occ, per jack and correct address is 12080 w mcmillan rd; Phone #: ###-#### Internet Inspection Request from: Victoria Beall 1. need permit for core and shell 2. 517.78- grounding of metal parts for xray 3. 110.3- listing and labeling of xray equipment.
|
Final | 1/11/2007 | 1/11/2007 | 1/11/2007 | P | FAIL |
Jack Frank
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no permit for core and shell bld06-01466, address on blding is 12080 w mcmillian, job not ready needs permit for added fixtures, cord shall not pass through ceiling N W rm , install all blank covers called, everything ok except items noted
|
Electrical Rough-In | 12/13/2006 | 12/14/2006 | 12/14/2006 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/13/2006 at 6:10:50 PM. grid ceilings ok
|
Permanent Service | 11/30/2006 | 11/30/2006 | 11/30/2006 | P | PASS |
Jack Frank
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy p/s u/g new ok
|
Rough-In Permanent Service | 11/28/2006 | 11/28/2006 | 11/28/2006 | P | PART |
Jack Frank
|
|
|
dennis ; Phone #: ###-#### Internet Inspection Request from: Patricia p/s not ready, r/i ok for 1/2 of front desk walls
|
Electrical Rough-In | 11/8/2006 | 11/8/2006 | 11/8/2006 | P | PART |
Jack Frank
|
|
|
dennis ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie all walls ok
|
Electrical Rough-In | 11/7/2006 | 11/8/2006 | 11/8/2006 | A | CANC |
Jack Frank
|
|
|
denis - partial ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith contr called
|
Electrical Rough-In | 11/7/2006 | 11/7/2006 | 11/7/2006 | P | PART |
Bob Reichert
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles north and east walls only ok to cover, need to look at center, west and south areas for strapping, ko seals, 1 1/4" for mc , ground boxes, make-up
|
Electrical Rough-In | 10/16/2006 | 10/16/2006 | 10/16/2006 | P | PART |
Jim Schmer
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles front soffet, center flex for units on roof - ok
|
Electrical Rough-In | 9/1/2006 | 9/1/2006 | 9/1/2006 | P | PASS |
William E Thomas
|
|
|
Dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt slab work ok
|
Electrical Rough-In | 8/30/2006 | 8/30/2006 | 8/30/2006 | P | PART |
Bob Reichert
|
|
|
This is for an underground conduit inspection, call Dennis at ###-#### with any questions.; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa u/g thru center and north side bldg ok to cover
|
Electrical Rough-In | 8/15/2006 | 8/16/2006 | 8/16/2006 | A | PASS |
Bob Reichert
|
|
|
Uffer ground inspection.; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa ok to cover gec
|