Final | 11/15/2006 | 11/15/2006 | 11/15/2006 | P | PASS |
Jack Frank
|
|
|
Final re-inspection, please call homeowner Greg or Jean Jacobsen @ ###-#### prior to arrival. Please call Todd Hall @ ###-#### upon completion.; Phone #: ###-#### Internet Inspection Request from: todd hall
|
Final | 11/9/2006 | 11/13/2006 | 11/13/2006 | A | FAIL |
Jack Frank
|
|
|
FINAL INSPECTIONPLEASE CALL AJ WITH INSPECTION QUESTIONS AND/OR RESULTS; Phone #: ###-#### Internet Inspection Request from: todd hall corr called left message 314.16 box fill island counter recept, 250.148 grd all metal boxes island, 300.14 short grd wires island counter, corrections for owner 110.26 shall remove cabinets in garage for panel clearence, 410.8 needs clearence for fixture MB closet new shelf above fixture
|
Rough-In Permanent Service | 9/20/2006 | 9/20/2006 | 9/20/2006 | P | PART |
Pat Lass
|
|
|
Rough in for floor heat system in master bath- please call Todd with inspection results after inspection; Phone #: ###-#### Internet Inspection Request from: todd hall R/I Ok no service
|
Electrical Rough-In | 8/18/2006 | 8/21/2006 | 8/21/2006 | P | PART |
Pat Lass
|
|
|
kitchen lighting and receps. Master bath floor heat.; Phone #: ###-#### Internet Inspection Request from: todd hall this is for 2 bathrooms and kitchen 2nd bath recep and floor heat to be inspected later
|