Final | 8/21/2006 | 8/23/2006 | 8/23/2006 | A | FAIL |
Jack Frank
|
|
|
jessica - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 230.28 needs stiff let to oppose strain not guy kit, 110.3(B) use manufactures breakers only, 250.64(B) protect #8 GEC or install #6, 250.52(A)(1)or104(A)(1) grd or bond water system corr. called
|
Permanent Service | 8/18/2006 | 8/21/2006 | 8/21/2006 | A | NH |
Pat Lass
|
|
|
dilbert; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no access called will reschedual
|