Permit Information
Permit NumberELE06-03123
StatusFinaled
Name GOODMAN ELECTRIC
Site Address 1400 W RANCH RD
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/21/20076/22/20076/22/2007APASS
DetailsPat Lass
Phone #: ###-####
Final6/21/20076/21/20076/21/2007PFAIL
DetailsPat Lass
dave or roger ###-#### Phone #: ###-####
410.8(B) shall provide globe guard for closet light, BCC disposal shall be wired, room count on permit shall be at least 12 rooms
Final6/14/20076/14/20076/14/2007PFAIL
DetailsBob Reichert
dave ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told contr, he called for inspection, left corr notice, 406.5 recpt faceplates shall seat against mounting surface, 406.4(D) recpt faces shall be flush with or project from faceplate,406.4 recpts shall be securely fastened in place(laundry), 408.4 circuit directory shall be clear, concise, and explanatory for each circuit and purpose, 210.52(A)(2) 2' wall space shall have recpt behind shower, 110.3(B) listed equip shall be installed per mfgr's instructions(no reverse polarity), 410.8(B) shall provide globe guard for closet light, BCC disposal shall be wired, room count on permit shall be at least 12 rooms
Electrical Rough-In1/5/20071/8/20071/8/2007APASS
DetailsPat Lass
roger; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Permanent Service10/2/200610/3/200610/3/2006APASS
DetailsPat Lass
###-####
P/S U/G N Ok
Electrical Rough-In9/29/200610/2/200610/2/2006APART
DetailsPat Lass
roger; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
electrode ok for concrete after footing is cleaned off.
Permanent Service9/21/20069/21/20069/21/2006PFAIL
DetailsPat Lass
roger ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
concrete encased electrode required because the re-bar is only 3/8"