Permit Information
Permit NumberELE06-03160
StatusFinaled
Name ELCOR ELECTRIC
Site Address 2220 W MADISON AVE
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Addition: Remodel with a bedroom addition. electrical work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/5/200612/5/200612/5/2006PPASS
DetailsPat Lass
Back door behind gate is open; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
Final12/1/200612/4/200612/4/2006ANH
DetailsPat Lass
Side door behind gate is open; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
gates locked
Final11/30/200612/1/200612/1/2006ANH
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
called contractor and left message no access
Final11/29/200611/29/200611/29/2006PNR
DetailsPat Lass
SIDE DOOR BEHIND GATE IS OPEN!!!; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
this is for a bedroom, kitchen, bathroom and some cut-in cans in the basement.
contractor will add 3 rooms to the permit. and make sure that everything works for final
Electrical Rough-In9/28/20069/28/20069/28/2006PPASS
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
Electrical Rough-In9/18/20069/18/20069/18/2006APART
DetailsBob Reichert
Wall Inspection; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ric ok from door to bedroom addition, no stair or kitchen areas
Rough-In Permanent Service8/28/20068/29/20068/29/2006APART
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
electrode ok
P/S O/H R Ok to transfer power
Permanent Service8/28/20068/28/20068/28/2006PCANC
DetailsJack Frank
As early as possible; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen see added r/i
Electrical Rough-In8/28/20068/28/20068/28/2006PPART
DetailsJack Frank
As early as possible; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen electrode ok for concrete cover only
Permanent Service8/24/20068/24/20068/24/2006PFAIL
DetailsBob Reichert
Inspection for Afternoon. Thank you!; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contr, left corr notice, nec 230.24(A)exc3, bottom of drip loop shall be min 18" above roof line, 250.52(A)(3) and BCC concrete encased electrode shall be installed