Final | 2/6/2007 | 2/6/2007 | 2/6/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/6/2007 at 9:13:19 AM. Contact: ###-####. called contr to finish tightening recpts, corr made, ok to final
|
Final | 1/30/2007 | 1/31/2007 | 1/31/2007 | A | FAIL |
Bob Reichert
|
|
|
ZANE PLEASE CALL FIRST TO GET CODE; Phone #: ###-#### Internet Inspection Request from: Darla Downs called, left corr notice, nec 352.30 rnc shall be strapped within 3' of meter, 210.70(A)(2) lighting fixture shall be installed at exit to garage, 406.4 receptacles shall be securely mounted, NOTE: no u/g seen for post light or gate
|
Rough-In Permanent Service | 8/28/2006 | 8/30/2006 | 8/30/2006 | P | PASS |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Zane Robertson ri ok p/s u/g n ok
|