Final | 8/23/2007 | 8/23/2007 | 8/23/2007 | P | PASS |
Jack Frank
|
|
|
final for permit owner secured elect contr. to take over job
|
Electrical Rough-In | 4/16/2007 | 4/16/2007 | 4/16/2007 | P | PASS |
William E Thomas
|
|
|
Bill; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ri ok
|
Electrical Rough-In | 3/29/2007 | 3/30/2007 | 3/30/2007 | A | FAIL |
Jack Frank
|
|
|
bobby; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr. posted met owner partial correction only job not ready, and owner has done prior wiring without permit and covered without inspection , p/s needs upgrade, he has enclosed service entrance mast needs clearence over roof, panel in closet, 300.4 nail plates and 11/4", 314.20 boxes not flush with siding, 404.9(B) needs grd pigtails for switches, 250.148 grd all metal boxes, 110.3(B) install recess fixture for manufacture clearence from combustible material, BCC no violations retained COW
|