Electrical Rough-In | 11/8/2006 | 11/8/2006 | 11/8/2006 | P | CANC |
Bob Reichert
|
|
|
We have made the corrections you required. ALSO we replaced a pole light on the west end of of the string of power / light poles and re-fed it. Please inspect it also and I will update the Final Job Value to include this work.Thanks !!!! (6080628aaa)Tech/Jason/###-####. ; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell see final, wrong type pequest
|
Final | 11/8/2006 | 11/8/2006 | 11/8/2006 | P | PASS |
Bob Reichert
|
|
|
We have made the corrections you required. ALSO we replaced a pole light on the west end of of the string of power / light poles and re-fed it. Please inspect it also and I will update the Final Job Value to include this work.Thanks !!!! (6080628aaa)Tech/Jason/###-####. ; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell corrections made, ok to final
|
Final | 8/31/2006 | 8/31/2006 | 8/31/2006 | P | FAIL |
Jack Frank
|
|
|
We ran a new pipe and wires from an existing pole mounted panel to a light on another pole through the customer's trench.Mounted a bell box with switch up near the light.This is nearest the southern most entrance into the mobile park from Shoshone.(6080628aaa)Tech/Jason/###-####.Thanks!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell partial corr. posted called 110.3(A&B) are lugs in meterbase approved for more than 1 conductor?, streetlight service shall meet all grding and bonding requirements per art. 250, 550..31 address service as code noted states for park wiring, shall address tap rules 240.21, 240.51(B) evidence of overfusing use type S adapters and fuses, B C C no violations to be retained
|
Electrical Rough-In | 8/31/2006 | 8/31/2006 | 8/31/2006 | P | PART |
Jack Frank
|
|
|
We ran a new pipe and wires from an existing pole mounted panel to a light on another pole through the customer's trench.Mounted a bell box with switch up near the light.This is nearest the southern most entrance into the mobile park from Shoshone.(6080628aaa)Tech/Jason/###-####.Thanks!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell cover for u/g conduit only
|