Permit Information
Permit NumberELE06-03275
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 330 N MILWAUKEE ST
Project NameTHE CHEESECAKE FACTORY BTS
Customer Number2614
ePlanReview 
Description
Electrical Permit - New: Install cold cathode and related wiring devices as per plans & specs.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/5/200612/5/200612/5/2006PPASS
DetailsBob Reichert
code marks on boiler ok, ok to final, signed occ card
Final11/20/200611/20/200611/20/2006PPART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 11/20/2006 at 7:02:47 AM. Contact: ###-####. met contr, left corr notice,signed t/o card, nec 110.3(B) and BCC 4-05-33(A)(B) all electric equipment shall be listed by a nationally recognized testing laboratory (boiler), Note; correction shall be made within 2 weeks or further action will be taken, such as removal of power
Electrical Rough-In11/17/200611/17/200611/17/2006APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 11/17/2006 at 6:45:07 AM. Contact: ###-####. ceiling main area ok to cover
Permanent Service11/15/200611/16/200611/16/2006APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 11/15/2006 at 7:25:14 PM. Contact: ###-####. p/s u/g n ok, new line-up
Electrical Rough-In11/13/200611/13/200611/13/2006APART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 11/13/2006 at 6:54:34 AM. Contact: ###-####.rear ceiling only ok to cover
Electrical Rough-In10/30/200610/30/200610/30/2006APART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 10/30/2006 at 6:53:51 AM. Contact: ###-####. lobby walls and clg, bakery ceiling ok to cover
Electrical Rough-In10/26/200610/27/200610/27/2006APART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 10/26/2006 at 4:51:27 PM. Contact: ###-####. baths, mech room walls, lighting control wall, soffits ok to cover
Electrical Rough-In10/25/200610/25/200610/25/2006APART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 10/25/2006 at 7:20:31 AM. Contact: ###-####. main area soffits only ok to cover
Electrical Rough-In10/23/200610/23/200610/23/2006PPART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 10/23/2006 at 11:27:41 AM. Contact: ###-####. walls ok by office hall and rooms east side of hall
Electrical Rough-In10/20/200610/20/200610/20/2006APART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 10/20/2006 at 6:41:22 AM. Contact: ###-####. ok to cover walls prep kitchen and mgr's office only
Electrical Rough-In10/17/200610/17/200610/17/2006APART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 10/17/2006 at 7:18:17 AM. Contact: ###-####. main cook-line wall ok to cover
Electrical Rough-In10/12/200610/12/200610/12/2006APART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 10/12/2006 at 6:59:32 AM. Contact: ###-####. perimeter walls ok to cover
Electrical Rough-In10/5/200610/6/200610/6/2006PPASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 10/5/2006 at 1:17:12 PM. Contact: ###-####. north 1/2 main floor ok to cover u/g, 3 sign boxes on mezz ok to cover
Electrical Rough-In10/3/200610/4/200610/4/2006APART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 10/3/2006 at 11:44:30 AM. Contact: ###-####. south 1/2 u/g ok to cover- entry area
Electrical Rough-In9/28/20069/29/20069/29/2006APART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 9/28/2006 at 2:13:08 PM. Contact: ###-####. ok to pour gec, u/g ok to pour
Conference9/5/20069/5/20069/5/2006PCANC
DetailsBob Reichert
Scheduled by a contractor via Hello! on 9/5/2006 at 11:11:42 AM. Contact: ###-####. wrong permit, see ele06-02254