Final | 11/22/2006 | 11/27/2006 | 11/27/2006 | A | PASS |
Jack Frank
|
|
|
Project Mgr-Kiel ###-####; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson survey posted 210.52(C)(5) exception, outlet end of pen. counter countertop extends more than 6" beyond its base, 408.4 panel directory shall be specific called final ok
|
Final | 11/22/2006 | 11/22/2006 | 11/22/2006 | A | CANC |
Jim Schmer
|
|
|
Jim - South-west corner of project second Bldg; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson no access until monday jms
|
Final | 11/21/2006 | 11/21/2006 | 11/21/2006 | P | FAIL |
Jim Schmer
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson could not find, place is a ___ (mess) with address not on all buildings and not in an order that I know of. Pat may have a map, but other inspectors don't. JMS
|
Permanent Service | 9/11/2006 | 9/11/2006 | 9/11/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to backfill, p/s u/g n ok 2 meters
|
Rough-In Permanent Service | 9/8/2006 | 9/8/2006 | 9/8/2006 | P | PASS |
William E Thomas
|
|
|
This is for a ufer inspection.; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson 1. ufer ok 2. p/s u/g n ok 2meters required
|
Rough-In Permanent Service | 9/6/2006 | 9/7/2006 | 9/7/2006 | A | PART |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson R/I Ok Electrode ok for concrete
|
Rough-In Permanent Service | 9/5/2006 | 9/6/2006 | 9/5/2006 | A | CANC |
Pat Lass
|
|
|
lisa; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: Tracy Robertson
|