Final | 4/13/2007 | 4/13/2007 | 4/13/2007 | P | PASS |
Bob Reichert
|
|
|
The builder said the door was unlocked and building available for insp. The UL floor box sheet is on the front entry vestibule window. Thanks Phone #: ###-#### corr made, ok to cover
|
Final | 4/11/2007 | 4/12/2007 | 4/12/2007 | A | NH |
Mike Kinnear
|
|
|
The cut sheets showing UL for floor boxes is on the front vestibule window, if locked there is a key in a magnetic key holder under the CT can or meter base Thank You Phone #: ###-#### no access due to paint fumes called contractor
|
Final | 4/11/2007 | 4/12/2007 | 4/11/2007 | A | CANC |
Bob Reichert
|
|
|
We put the cut sheets showing the UL listing for the floor boxes on the front entry vestibule window Phone #: ###-#### Inspection cancelled from web by: Jamie Winters
|
Final | 4/3/2007 | 4/4/2007 | 4/4/2007 | A | FAIL |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left corr notice, 110.26(F)(1) dedicated electrical space shall be 6' over panels, 314.27 floor boxes shall be listed specifically for receptacles in floor, BCC recepts shall operate
|
Final | 3/30/2007 | 3/30/2007 | 3/30/2007 | P | PART |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called contr, told to strap riser, check recpt operation by water heater, west side, sw recpt, n side trips gfci in other room, no power in front north wall, floor box cover not approved, since recpts flooded
|
Conference | 3/19/2007 | 3/19/2007 | 3/19/2007 | A | DONE |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/19/2007 at 6:24:30 AM. Contact: ###-####. talked about pre-final points, if any, while doing ri for dropped clg
|
Electrical Rough-In | 3/19/2007 | 3/19/2007 | 3/19/2007 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/19/2007 at 6:23:48 AM. Contact: ###-####. ok to cover grid ceiling only
|
Electrical Rough-In | 1/17/2007 | 1/17/2007 | 1/17/2007 | P | PASS |
Bob Reichert
|
|
|
MIKE; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ric ok
|
Electrical Rough-In | 1/16/2007 | 1/16/2007 | 1/16/2007 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/16/2007 at 7:45:29 AM. Contact: ###-####. called left corr notice, nec 110.12(A) unused openings in boxes shall be closed, 330.30(A) mc cable bend radius shall be 7x diameter of cable,330.30(B) mc cable sahll be strapped within 12" of box, 300.4(A)&(D) edge of bored holes and mc cable shall be 1 1/4" from edge of framing members
|
Permanent Service | 1/3/2007 | 1/4/2007 | 1/3/2007 | A | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
|
Electrical Rough-In | 12/29/2006 | 1/2/2007 | 1/2/2007 | A | PASS |
Bob Reichert
|
|
|
mike - uffer ; Phone #: ###-#### - ###-#### Internet Inspection Request from: Patricia Smith ok to backfill gec
|
Electrical Rough-In | 12/27/2006 | 12/27/2006 | 12/27/2006 | P | PART |
Pat Lass
|
|
|
###-#### - mike Note; ufier; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles electrode ok for concrete
|
Electrical Rough-In | 12/7/2006 | 12/7/2006 | 12/7/2006 | P | PASS |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### or ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover u/g outside bldg
|
Electrical Rough-In | 12/6/2006 | 12/7/2006 | 12/7/2006 | A | FAIL |
Jack Frank
|
|
|
We need the underground conduits to the light poles inspected for backfill, Thanks; Phone #: ###-#### Internet Inspection Request from: Jamie Winters corr. called T300.5 u/g shall 24" all locations parking lot
|
Conference | 12/6/2006 | 12/6/2006 | 12/6/2006 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/6/2006 at 7:13:53 AM. Contact: ###-####. Inspection cancelled from web by: Jamie Winters
|
Electrical Rough-In | 9/13/2006 | 9/14/2006 | 9/14/2006 | A | PASS |
Mike Kinnear
|
|
|
mike - underground insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok cover under slab conduit
|