Permit Information
Permit NumberELE06-03427
StatusFinaled
Name A M E ELECTRIC
Site Address 2833 S VICTORY VIEW WAY
Project NameSimply Cats
Customer Number 
ePlanReview 
Description
wiring outlets, lights, exterior lighting, panels, light poles per initial cert of value $88,278.00 ///final value is $96,865 per faxed document 6-11-07ps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/13/20074/13/20074/13/2007PPASS
DetailsBob Reichert
The builder said the door was unlocked and building available for insp. The UL floor box sheet is on the front entry vestibule window. Thanks Phone #: ###-#### corr made, ok to cover
Final4/11/20074/12/20074/12/2007ANH
DetailsMike Kinnear
The cut sheets showing UL for floor boxes is on the front vestibule window, if locked there is a key in a magnetic key holder under the CT can or meter base Thank You Phone #: ###-#### no access due to paint fumes called contractor
Final4/11/20074/12/20074/11/2007ACANC
DetailsBob Reichert
We put the cut sheets showing the UL listing for the floor boxes on the front entry vestibule window Phone #: ###-#### Inspection cancelled from web by: Jamie Winters
Final4/3/20074/4/20074/4/2007AFAIL
DetailsBob Reichert
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left corr notice, 110.26(F)(1) dedicated electrical space shall be 6' over panels, 314.27 floor boxes shall be listed specifically for receptacles in floor, BCC recepts shall operate
Final3/30/20073/30/20073/30/2007PPART
DetailsBob Reichert
Mike; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called contr, told to strap riser, check recpt operation by water heater, west side, sw recpt, n side trips gfci in other room, no power in front north wall, floor box cover not approved, since recpts flooded
Conference3/19/20073/19/20073/19/2007ADONE
DetailsBob Reichert
Scheduled by a contractor via Hello! on 3/19/2007 at 6:24:30 AM. Contact: ###-####. talked about pre-final points, if any, while doing ri for dropped clg
Electrical Rough-In3/19/20073/19/20073/19/2007APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 3/19/2007 at 6:23:48 AM. Contact: ###-####. ok to cover grid ceiling only
Electrical Rough-In1/17/20071/17/20071/17/2007PPASS
DetailsBob Reichert
MIKE; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ric ok
Electrical Rough-In1/16/20071/16/20071/16/2007PFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 1/16/2007 at 7:45:29 AM. Contact: ###-####. called left corr notice, nec 110.12(A) unused openings in boxes shall be closed, 330.30(A) mc cable bend radius shall be 7x diameter of cable,330.30(B) mc cable sahll be strapped within 12" of box, 300.4(A)&(D) edge of bored holes and mc cable shall be 1 1/4" from edge of framing members
Permanent Service1/3/20071/4/20071/3/2007APASS
DetailsBob Reichert
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
Electrical Rough-In12/29/20061/2/20071/2/2007APASS
DetailsBob Reichert
mike - uffer ; Phone #: ###-#### - ###-#### Internet Inspection Request from: Patricia Smith ok to backfill gec
Electrical Rough-In12/27/200612/27/200612/27/2006PPART
DetailsPat Lass
###-#### - mike Note; ufier; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
electrode ok for concrete
Electrical Rough-In12/7/200612/7/200612/7/2006PPASS
DetailsBob Reichert
Mike; Phone #: ###-#### or ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover u/g outside bldg
Electrical Rough-In12/6/200612/7/200612/7/2006AFAIL
DetailsJack Frank
We need the underground conduits to the light poles inspected for backfill, Thanks; Phone #: ###-#### Internet Inspection Request from: Jamie Winters corr. called
T300.5 u/g shall 24" all locations parking lot
Conference12/6/200612/6/200612/6/2006ACANC
DetailsBob Reichert
Scheduled by a contractor via Hello! on 12/6/2006 at 7:13:53 AM. Contact: ###-####. Inspection cancelled from web by: Jamie Winters
Electrical Rough-In9/13/20069/14/20069/14/2006APASS
DetailsMike Kinnear
mike - underground insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok cover under slab conduit