Final | 6/11/2009 | 6/11/2009 | 6/11/2009 | P | PASS |
Mike Kinnear
|
|
|
corrections made ok final
|
ELE-Aging Inspection | 10/29/2008 | 10/29/2008 | 10/29/2008 | | DONE |
Bob Reichert
|
|
|
see doc expire, no activity
|
DOC - Permit Expired | 10/29/2008 | 10/29/2008 | 10/29/2008 | A | PASS |
Bob Reichert
|
|
|
no activity, contractor didn't call, expire permit
|
ELE-Aging Inspection | 8/26/2008 | 8/26/2008 | 8/26/2008 | | DONE |
Bob Reichert
|
|
|
talked to contractor, he said UL will be here next week, will advise of outcome for printing press, no esc this project
|
ELE-Aging Inspection | 5/29/2008 | 5/29/2008 | 5/30/2008 | | DONE |
Bob Reichert
|
|
|
waiting for contractor to call with status
|
ELE-Aging Inspection | 3/3/2008 | 3/3/2008 | 3/3/2008 | | DONE |
Bob Reichert
|
|
|
called, left message to return call to check status
|
Permanent Service | 9/28/2006 | 9/28/2006 | 9/28/2006 | P | FAIL |
Bob Reichert
|
|
|
DAVE BRADSHAW - CALL & HE WILL MEET @ JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail met contr, left corr notice, nec 110.26(F)(1)(a) there shall be no foreign piping over the electrical installation equal to the width and depth 6' above the equipment, 110.2 equipment shall be acceptable only if approved, BCC 4-05-33(A)&(B) electrical equipment shall bear the listing mark of an approved testing laboratory,NOTE: corrections shall be made within 2 weeks or further action will be taken, such as removing power
|