Final | 7/17/2007 | 7/17/2007 | 7/17/2007 | P | PASS |
Bob Reichert
|
|
|
ok to final
|
Final | 7/16/2007 | 7/17/2007 | 7/17/2007 | P | NH |
Bob Reichert
|
|
|
sarah Phone #: ###-#### called, left message, left card
|
Final | 7/12/2007 | 7/13/2007 | 7/13/2007 | P | FAIL |
William E Thomas
|
|
|
SARAH Phone #: ###-#### 410.8 1st room closet
|
Rough-In Permanent Service | 1/29/2007 | 2/1/2007 | 2/1/2007 | P | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/29/2007 at 1:30:57 PM. Contact: ###-####. wrong type request, see ri
|
Electrical Rough-In | 2/1/2007 | 2/1/2007 | 2/1/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/29/2007 at 1:30:57 PM. Contact: ###-####. corr made, ric ok
|
Rough-In Permanent Service | 1/10/2007 | 1/23/2007 | 1/23/2007 | P | CANC |
Bob Reichert
|
|
|
matt ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see ri and ps
|
Electrical Rough-In | 1/23/2007 | 1/23/2007 | 1/23/2007 | P | FAIL |
Bob Reichert
|
|
|
matt ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith met owner, service was ok, ri corrections are: nec 312.5 all conductors entering enclosures shall have abrasion protection, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from face of framing members, 110.12(C) there shall be no broken parts(boxes), 250.53(D)(2) supplementary grounding electrode shall be installed, 334.30 nm cable shall be supported within 12" of box and 8" for plastic, BCC all make-up shall be done
|
Permanent Service | 1/23/2007 | 1/23/2007 | 1/23/2007 | P | PASS |
Bob Reichert
|
|
|
matt ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s u/g rec ok
|
Conference | 11/9/2006 | 11/13/2006 | 11/13/2006 | A | DONE |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/9/2006 at 4:11:22 PM. Contact: ###-####. agreed for subpanel, but told owner needs to run load calcs and probably requires 200A service, talked about afcis and general elect
|