Final | 11/29/2006 | 11/29/2006 | 11/29/2006 | A | PASS |
Jack Frank
|
|
|
Please call Brett Ogata at ###-#### before going to the property. He will meet you. Internet Inspection Request from: Latisha Peltier ok survey 410.4 (D) remove track light from zone, 408.4 panel directory called left message
|
Final | 11/28/2006 | 11/28/2006 | 11/28/2006 | P | FAIL |
Jack Frank
|
|
|
Please call Sean at ###-#### if any problems or questions. Thank you. Internet Inspection Request from: Latisha Peltier called needs furniture moved and someone there at time of final
|
Permanent Service | 10/17/2006 | 10/17/2006 | 10/17/2006 | P | PASS |
Bob Reichert
|
|
|
Internet Inspection Request from: Latisha Peltier corr made, p/s o/h n ok
|
Permanent Service | 10/13/2006 | 10/13/2006 | 10/13/2006 | P | FAIL |
Bob Reichert
|
|
|
Internet Inspection Request from: Latisha Peltier called,left correction notice, nec 250.24(A) a grounded service shall have a grounding electrode conductor connected to the grounded service conductor, 250.32(B) grounded conductor shall not be connected to equipment grounding conductor at sub-panel
|
Electrical Rough-In | 9/19/2006 | 9/19/2006 | 9/19/2006 | P | PASS |
Bob Reichert
|
|
|
Internet Inspection Request from: Latisha Peltier called contr, ric ok
|