Final | 4/17/2007 | 4/17/2007 | 4/17/2007 | P | PASS |
Bob Reichert
|
|
|
chad - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
Final | 3/27/2007 | 3/28/2007 | 3/27/2007 | A | CANC |
Bob Reichert
|
|
|
Call 1/2 hour before inspection to gain entry into the house. Plese call Chad at the listed number. thank you Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|
Permanent Service | 10/12/2006 | 10/13/2006 | 10/13/2006 | A | PASS |
Mike Kinnear
|
|
|
chad ###-#### not sure if perm ser has been insp??please call chad 1st p/s o/h n ok corrections made
|
Electrical Rough-In | 10/5/2006 | 10/5/2006 | 10/5/2006 | P | PASS |
Jack Frank
|
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i ok corrections made
|
Rough-In Permanent Service | 10/2/2006 | 10/2/2006 | 10/2/2006 | P | FAIL |
Jack Frank
|
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called outside of house ok for cover only, 210.52(A) required outlets 2 in din rm 1 in liv rm, 300.14 grds cut short, 250.148 grd all metal boxes, 230.6 no service entrance conductors allowed in wall (SER) cable, 230.24 needs 8ft clearence from drip loop to roof
|
Rough-In Permanent Service | 9/29/2006 | 10/2/2006 | 10/2/2006 | A | CANC |
Jack Frank
|
|
|
chad - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr canceled
|