Final | 10/11/2006 | 10/12/2006 | 10/12/2006 | A | PASS |
Mike Kinnear
|
|
|
need final inspection on service. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH t/s u/g n ok
|
Temporary Service | 10/12/2006 | 10/12/2006 | 10/12/2006 | P | PASS |
Mike Kinnear
|
|
|
need final inspection on service. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH t/s u/g n ok
|
Temporary Service | 10/9/2006 | 10/10/2006 | 10/10/2006 | P | FAIL |
Mike Kinnear
|
|
|
READY FOR TEMP POWER INSPECTION. POLE AT SECTOR BOX IN FRONT YARD. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corrections nec590.6(B)(1) 30 amp 240 volt receptacle shall be gfci protected nec406.8(B) inuse cover is broken BCC shall use a ground choke or plastic romex connector for the grounding conductor to enter the enclosure
|
Temporary Service | 9/22/2006 | 9/22/2006 | 9/22/2006 | P | FAIL |
Mike Kinnear
|
|
|
need temp service inspection on pole. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH no temp service at is address -- unable to get into the building. but was able to see back of panel it is not rain tight panel. (panel exposed to the weather)
|