Final | 3/27/2007 | 3/27/2007 | 3/27/2007 | P | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 3/27/2007 at 9:58:47 AM. Contact: ###-####. final ok
|
Electrical Rough-In | 3/20/2007 | 3/21/2007 | 3/21/2007 | A | PASS |
Bob Reichert
|
|
|
ceiling inspection please ###-#### kendall ok to cover ceilings
|
Rough-In Permanent Service | 1/23/2007 | 1/23/2007 | 1/23/2007 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/23/2007 at 9:17:48 AM. Contact: ###-####. needs to terminate GEC to neutral bus, and bond water p/s u/g new ok for 1 tenant space
|
Electrical Rough-In | 1/12/2007 | 1/12/2007 | 1/12/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/12/2007 at 7:33:20 AM. Contact: ###-####. offices ric ok, corrections made, still working on addressing
|
Rough-In Permanent Service | 1/10/2007 | 1/10/2007 | 1/10/2007 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/10/2007 at 10:21:02 AM. Contact: ###-####. called, told contr that corrections weren't ready, wrote corr notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members or shall use steel plates, BCC address shall be posted, talked with bldr, they are requesting change of adress, told each location needs address
|
Electrical Rough-In | 1/4/2007 | 1/4/2007 | 1/4/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/4/2007 at 8:15:06 AM. Contact: ###-####. walls office areas and hard lids only ok to cover
|
Electrical Rough-In | 10/4/2006 | 10/5/2006 | 10/5/2006 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/4/2006 at 6:16:21 PM. Contact: ###-####.u/g ok
|