Final | 1/29/2008 | 1/29/2008 | 1/29/2008 | P | PASS |
Jack Frank
|
|
|
p/s ok for final 370 forgot to add it at time of p/s
|
Permanent Service | 10/10/2006 | 10/10/2006 | 10/10/2006 | P | PASS |
Bob Reichert
|
|
|
erin; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, p/s u/g rec ok
|
Permanent Service | 10/9/2006 | 10/9/2006 | 10/9/2006 | P | FAIL |
Bob Reichert
|
|
|
bob; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, corr not made, no address
|
Permanent Service | 9/26/2006 | 9/27/2006 | 9/27/2006 | A | FAIL |
Bob Reichert
|
|
|
bob; Phone #: ###-#### Pleae call for code Internet Inspection Request from: Cathy Chiles called, left corr notice, BCC address and job id sticker shall be posted,nec 352.30 rnc shall be securely fastened within 3' of termination, 250.64(B) gec shall be securely fastened to surface which carried, 250.50, 250.52(A)(1) water pipr shall be part of grounding electrode system, 110.12(A) unused openings shall be closed, 334.30 nm cable shall be supported within 12" of panel, 110.26(A)(2) min 30" work space shall be provided in front of sub-panel
|