Final | 12/21/2006 | 12/22/2006 | 12/22/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day corr made ok to final
|
Final | 12/20/2006 | 12/20/2006 | 12/20/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day called, left corr notice, Told builder that there is not supposed to be an occupant prior to inspection. NEC 314.23 (A) boxes shall be securely mounted, 406.4(D) recpt faces shall be flush with or project from faceplates, 422.31(B) dishwasher shall have lock out provisions, 110.12(C) gfci in mbr shall not be damaged or deteriorated,BCC all work shall be done, disposal wired, a/c wired
|
Permanent Service | 10/11/2006 | 10/11/2006 | 10/11/2006 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day p/s u/g new ok
|
Electrical Rough-In | 10/9/2006 | 10/9/2006 | 10/9/2006 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day r/i ok only
|
Electrical Rough-In | 10/3/2006 | 10/4/2006 | 10/4/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day corr. called 314.16 box fill, 300.4 nail plates and 11/4" 250.148 splice all equip grds together at boxes, 210.52(A&B) needs outlet wall space in kit. 250.24(A)(1)&(4) terminate GEC and bond to neutral bus, needs airtight recess fixtures, install all boxes, update permit for 11 rooms
|