ELE-Aging Inspection | 10/31/2007 | 10/31/2007 | 11/5/2007 | | DONE |
Jack Frank
|
|
|
job taken over by different contr
|
DOC - Permit Expired | 11/5/2007 | 11/5/2007 | 11/5/2007 | P | PASS |
Jack Frank
|
|
|
|
Conference | 10/3/2006 | 10/4/2006 | 10/4/2006 | A | DONE |
Bob Reichert
|
|
|
Conf at 8:30, if possible.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs talked about temp services required for a/c and how project would be built
|
Permanent Service | 10/3/2006 | 10/4/2006 | 10/4/2006 | A | PASS |
Bob Reichert
|
|
|
At 8:30, if possible.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs p/s exst meter pak n ok
|
Permanent Service | 9/28/2006 | 9/29/2006 | 9/29/2006 | A | FAIL |
Bob Reichert
|
|
|
Meter D.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs called left corr notice, 400.5(A) #4seow cord ampacity 70a, shall not use 100a breaker for overcurrent protection,408.4 circuit directory shall be provided, 110.21 sufficient marking shall be provided on panel to identify use,NOTE: shall supply portable trailer with 100a service
|