Final | 1/22/2007 | 1/22/2007 | 1/22/2007 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/22/2007 at 6:42:12 AM. ok
|
Final | 1/18/2007 | 1/18/2007 | 1/18/2007 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/18/2007 at 8:02:38 AM. Contact: ###-####. corr. fee due called 210.52(A&B) shall install outlet liv rm stub wall, also install outlet on SABC din. rm side of stub wall, 408.4 circuit directory shall be specific, 406.4(A B C) recepts loose in boxes, 250.122 shall not reduce size of conductors at 120V dryer recept, BCC note complete all trim, also stub wall was added after r/i inspection was done
|
Rough-In Permanent Service | 10/9/2006 | 10/10/2006 | 10/10/2006 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/9/2006 at 10:07:35 PM. Contact: ###-####. ric ok p/s u/g n ok
|
Rough-In Permanent Service | 10/2/2006 | 10/4/2006 | 10/4/2006 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/2/2006 at 7:49:39 AM. Contact: ###-####. called contr, left message, 334.30 nm cable shall be secured within 12" of box, flat cable shall not be stapled on edge (by garage door into house), 250.80 metal box shall be grounded, 300.4(A)&(D) edge of bored holes and nm cable shall be 11/4" from edge of framing member, 210.52(H) hallway over 10' shall have recpt installed, 210.52(A)(2) 2' wall in kitchen shall have recpt installed, BCC job id sticker shall be posted, all make-up shall be done
|