Final | 11/27/2006 | 11/28/2006 | 11/28/2006 | P | PASS |
Jack Frank
|
|
|
don; Phone #: ###-#### Note: please 1/2 hr prior to meet with - ###-#### GC Internet Inspection Request from: Cathy Chiles ok survey posted called314.20 box extension outlet in paneling below eating bar, 210.52(A) install outlet covered by sheetrock right of sliding door, 210.52(C) install gfci recept right of sink
|
Electrical Rough-In | 10/12/2006 | 10/12/2006 | 10/12/2006 | P | PASS |
Bob Reichert
|
|
|
don; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ric ok
|
Electrical Rough-In | 10/11/2006 | 10/11/2006 | 10/11/2006 | P | FAIL |
Bob Reichert
|
|
|
Don; Phone #: ###-#### go thru side gate on east side to addn. Internet Inspection Request from: Cathy Weisshaupt called, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 250.86 metal enclosures shall be grounded, 110.12(C) there shall be no damaged parts (nm west side up high), BCC all make-up shall be done
|
Electrical Rough-In | 10/5/2006 | 10/6/2006 | 10/6/2006 | P | NH |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Patricia Smith notice posted called
|