DOC - Permit Expired | 1/31/2019 | 1/31/2019 | 1/31/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity ofr over 180 days. This permit is EXPIRED. A new permit will be required to continue work.
|
ELE-Aging Inspection | 11/21/2018 | 11/21/2018 | 11/21/2018 | | DONE |
Daryl DeGrange
|
|
|
Waiting on owner to make decision weather to have corrections completed
|
ELE-Aging Inspection | 8/13/2018 | 8/13/2018 | 8/13/2018 | | DONE |
Daryl DeGrange
|
|
|
No change per Do Not Occupy Notice
|
ELE-Aging Inspection | 5/14/2018 | 5/14/2018 | 5/15/2018 | | DONE |
Daryl DeGrange
|
|
|
Property deemed unsafe to occupacy, plumbing and electrical code violations exist. Code compliance required for occupancy.
|
ELE-Aging Inspection | 2/12/2018 | 2/12/2018 | 2/12/2018 | | DONE |
Tom Saunders
|
|
|
address under review...MIS opened at location for Electrical, Plumbing, and HVAC
|
Final | 11/13/2017 | 11/15/2017 | 11/15/2017 | A | FAIL |
Tom Saunders
|
|
|
Art-please call 30 minutes prior to meet for access-Daryl ok''d realitor to change status from exp to iss so a final inspection can be done Phone #: ###-####....inspected the exterior of home and found multiple code violations...never inspected interior but viewed code violations thru window...at that time I spoke with Art the realtor/representative for home owner and discussed options for continuing inspection...at that time he decided there was no reason to continue with inspection...discussed hiring an electrical contractor to come to house and evaluate work that needs to done to bring homesite up to code
|
Permanent Service | 8/13/2007 | 8/13/2007 | 8/13/2007 | P | PASS |
Bob Reichert
|
|
|
matt Phone #: ###-#### corrections made, p/s o/h rec ok
|
Permanent Service | 8/9/2007 | 8/10/2007 | 8/10/2007 | A | FAIL |
Bob Reichert
|
|
|
matt Phone #: ###-#### met owner, left corr notice, 110.3(A) shall use only suitable electrical material, not water pipe ell at service, 250.24(A) shall install grounding and conductors to grounded service conductor at service, 250.52(A)(1) shall connect to water pipe within 5' of entering building, 250.53(D)(2) shall supplenent water pipe with ground rods, 344.30 shall support rigid pipe within 3' of conduit termination
|
Conference | 8/8/2007 | 8/9/2007 | 8/9/2007 | A | PASS |
Mike Kinnear
|
|
|
###-#### Matt-Please call early am to confirm who and when- Jim this is the guy who was at my desk that you spokewith you regarding roof pitch??? conf with home owner needs to move mast to new structure, 2 ground rods & remove or get new sub panel
|
Permanent Service | 8/7/2007 | 8/8/2007 | 8/8/2007 | A | FAIL |
Bob Reichert
|
|
|
Matt; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt met owner, left corr notice, nec 230.24(A) conductors shall have vertical clearance of min 8' above roof surface for distance of not less than 3' in all directions from edge of roof, did not do inspection of service since this became quite controversial, 370 left while owner was being too vocal and not willing to discuss further
|
Electrical Rough-In | 11/28/2006 | 11/29/2006 | 11/29/2006 | P | PART |
Bob Reichert
|
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover - but need to see boxes before devices installed in ceiling and walls
|
Electrical Rough-In | 11/17/2006 | 11/20/2006 | 11/20/2006 | P | FAIL |
Bob Reichert
|
|
|
Matt ###-#### met owner, left corr notice,nec 300.4 (A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members,250.86 metal boxes shall be grounded, 110.12(C) there shall be no broken parts, 210.52(A)(1) recpt shall be spaced such thay no point is over 6' from an outlet, 210.12(B) AFCI shall be provided for bedroom circuit outlets, lights and power,334.24 nm cable bend radius shall be 5 times diameter, BCC all make-up shall be done
|