DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/6/20077/6/20077/6/2007PPASS
DetailsJack Frank
dino; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok called needs to correct reversed polarity gfci kit
Rough-In Permanent Service12/28/200612/28/200612/28/2006PPASS
DetailsJack Frank
dino ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
p/s u/g new ok
Electrical Rough-In11/30/200612/1/200612/1/2006APASS
DetailsJack Frank
kim ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok survey posted plans not at job site if anything wrong will be corrected at final called let contr know
r/i ok
Rough-In Permanent Service10/10/200610/11/200610/11/2006AFAIL
DetailsBob Reichert
dino; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left corr notice, nec 210.52(A)(1) recpts shall be spaced so no point along wall is over 6' from outlet, 210.52(A)(2) recpt shall be installed in wall space over 2', 300.4(A) edge of bored hole shall be 1 1/4" from edge of framing member,404.8 center of breaker handle shall not be over 6'-7" above floor BCC approved set of plans shall be on job, address shall be posted