Final | 7/6/2007 | 7/6/2007 | 7/6/2007 | P | PASS |
Jack Frank
|
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok called needs to correct reversed polarity gfci kit
|
Rough-In Permanent Service | 12/28/2006 | 12/28/2006 | 12/28/2006 | P | PASS |
Jack Frank
|
|
|
dino ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s u/g new ok
|
Electrical Rough-In | 11/30/2006 | 12/1/2006 | 12/1/2006 | A | PASS |
Jack Frank
|
|
|
kim ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok survey posted plans not at job site if anything wrong will be corrected at final called let contr know r/i ok
|
Rough-In Permanent Service | 10/10/2006 | 10/11/2006 | 10/11/2006 | A | FAIL |
Bob Reichert
|
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left corr notice, nec 210.52(A)(1) recpts shall be spaced so no point along wall is over 6' from outlet, 210.52(A)(2) recpt shall be installed in wall space over 2', 300.4(A) edge of bored hole shall be 1 1/4" from edge of framing member,404.8 center of breaker handle shall not be over 6'-7" above floor BCC approved set of plans shall be on job, address shall be posted
|