Final | 11/29/2006 | 11/29/2006 | 11/29/2006 | P | PASS |
Bob Reichert
|
|
|
jack ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final
|
Final | 11/20/2006 | 11/21/2006 | 11/21/2006 | A | FAIL |
Bob Reichert
|
|
|
jack ; Phone #: ###-#### Internet Inspection Request from: Patricia Smithcalled left corr notice, nec 352.30(A) rnc shall be supported within 3' of panel, 680.26(B)(3) all metal fittings for pool cover shall be bonded, 680.22(A)(3) receptacle shall be between 10' and 20' of inside wall of pool
|
Permanent Service | 11/6/2006 | 11/7/2006 | 11/7/2006 | A | CANC |
Jack Frank
|
|
|
jack -- underground ; Phone #: ###-#### or ###-#### Internet Inspection Request from: Patricia Smith see added r/i
|
Electrical Rough-In | 11/7/2006 | 11/7/2006 | 11/7/2006 | A | PASS |
Jack Frank
|
|
|
jack -- underground ; Phone #: ###-#### or ###-#### Internet Inspection Request from: Patricia Smith ok corr. made
|
Electrical Rough-In | 11/2/2006 | 11/2/2006 | 11/2/2006 | P | FAIL |
Bob Reichert
|
|
|
jack - underground ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, left corr notice, nec 352.26 there shall not be over 360 degree total bend in rnc without pull points, 680.10 & 300.5 minimum burial depth shall be 18" for u/g conduit, BCC shall inspect all u/g before cover
|
Electrical Rough-In | 10/13/2006 | 10/16/2006 | 10/16/2006 | A | PART |
Jack Frank
|
|
|
pollie ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith E grid for pool ok
|
Rough-In Permanent Service | 10/12/2006 | 10/12/2006 | 10/12/2006 | P | PASS |
Jack Frank
|
|
|
bonding for pool-- jack; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie r/i for pool area u/g bonding, andyard light and R V recept ok no E grid, p/s o/h new ok
|