Final | 11/4/2006 | 11/6/2006 | 11/6/2006 | A | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack
|
Permanent Service | 10/19/2006 | 10/20/2006 | 10/20/2006 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 10/19/2006 at 5:53:00 PM. Contact: ###-####. P/S U/G N Ok
|
Permanent Service | 10/16/2006 | 10/17/2006 | 10/17/2006 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack corr. called left message, 300.4 nail plates and 11/4", 314.3&110.3(B) bond bushings for metal raceways in plastic boxes 300.10 bond bushings where RE washers are used, 330.30 & 348.30 strap MC and flex within 12" of everything,250.122T needs #10 equip grd at 4sq. for 50 amp circuit
|