Final | 5/9/2007 | 5/10/2007 | 5/10/2007 | P | PASS |
Jack Frank
|
|
|
The home owner said she would be home Thanks Don Phone #: ###-#### Internet Inspection Request from: Don Lustig ok
|
Electrical Rough-In | 10/18/2006 | 10/18/2006 | 10/18/2006 | A | PASS |
Jack Frank
|
|
|
will be on site at 8:00 am to fix the problems so any time later morning Thanks Don; Phone #: ###-#### Internet Inspection Request from: Don Lustig
|
Electrical Rough-In | 10/17/2006 | 10/17/2006 | 10/17/2006 | A | FAIL |
Jack Frank
|
|
|
Give me a call if any questions Thanks; Phone #: ###-#### Internet Inspection Request from: Don Lustig corr. called left message, 314.16 box fill old 3 gang N wall by door kit, 300.14 6" free length where work was done in old and new areas, 300.4 nail plates and 11/4" for cables parallel
|