Final | 10/25/2006 | 10/25/2006 | 10/25/2006 | P | PASS |
Bob Reichert
|
|
|
ok to final
|
Permanent Service | 10/25/2006 | 10/25/2006 | 10/25/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Fletcher corr made, p/s o/h rec ok
|
Permanent Service | 10/23/2006 | 10/24/2006 | 10/24/2006 | P | FAIL |
Bob Reichert
|
|
|
My cell phone number is ###-####, thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher called left corr notice, nec 408.4 circuit directory shall be complete, concise, and explanatory for each circuit, 110.3(B) listed equipment shall be installed and used in accordance with instructions-Sq D breakers, 314.15(A) fittings in wet locations shall be listed for use in wet locations(emt connectors to recpt), 348.12 fmc shall not be used in wet locations unless conductors are approved for wet locations, 352.30 rnc shall be secured within 3' of box
|