Permanent Service | 10/26/2006 | 10/27/2006 | 10/27/2006 | P | PASS |
Bob Reichert
|
|
|
reinsepction, we cannot label the panel until the power is connected as we cannot check which breaker goes to what, ID Power will not hook up the power without the inspection first Internet Inspection Request from: Rowdy Monroe called, still need abrasion protection, and final, p/s o/h rec ok
|
Permanent Service | 10/25/2006 | 10/26/2006 | 10/26/2006 | A | FAIL |
Bob Reichert
|
|
|
inspection for moving outside meter Internet Inspection Request from: Rowdy Monroe \alled left corr notice, nec 250.53(C)(2) shall install 2 grounding electrodes, 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be clear and concise, 230.24(A) service conductors shall be 8' above roof surface
|