Final | 4/29/2009 | 4/29/2009 | 4/29/2009 | P | PASS |
Bob Reichert
|
|
|
Michael Phone #: ###-#### ok to final, can't add esc response
|
Electrical Rough-In | 4/29/2009 | 4/29/2009 | 4/29/2009 | P | PASS |
Bob Reichert
|
|
|
Michael Phone #: ###-#### corrections made, ric ok, can't add esc
|
Electrical Rough-In | 4/7/2009 | 4/8/2009 | 4/8/2009 | A | CANC |
Mike Kinnear
|
|
|
Jared- call for access Phone #: ###-#### he to recall for tomorrow am
|
Electrical Rough-In | 4/6/2009 | 4/7/2009 | 4/7/2009 | A | FAIL |
Bob Reichert
|
|
|
Mike Phone #: ###-#### met owner, corrections, BCC all make-up shall be done, NEC 300.4 edge of bored holes shall be 1 1/4" from edge of framing member, 314.29 conduit body cover shall be accessible, 314.20 boxes shall be flush with finished surface
|
Rough-In Permanent Service | 12/17/2007 | 12/31/2007 | 12/31/2007 | P | CANC |
Bob Reichert
|
|
|
MIKE noTE: AFTER 2:00 PM Phone #: ###-#### wrong type request, see p/s
|
Permanent Service | 12/31/2007 | 12/31/2007 | 12/31/2007 | P | PASS |
Bob Reichert
|
|
|
MIKE noTE: AFTER 2:00 PM Phone #: ###-#### p/s o/h rec ok
|
Conference | 10/9/2007 | 10/10/2007 | 10/10/2007 | A | DONE |
Bob Reichert
|
|
|
mike - before 8:30 Phone #: ###-#### reviewed possible options to clear new garage with service conductors that currently feed house
|