Temporary Service | 11/8/2006 | 11/9/2006 | 11/9/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corr made, t/s o/h n ok
|
Temporary Service | 10/31/2006 | 10/31/2006 | 10/31/2006 | P | FAIL |
Bob Reichert
|
|
|
Temp pole; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken or cut parts- panel, recpt, 230.28 service mast shall be adequate strength to support conductors,230.26 point of attachment of service drop conductors shall be minimum 10' above grade, 110.12(A) unused openings shall be closed (bottom raceway), 110.3(B) only breakers shall be used per mfgrs listing and labelling, BCC job id sticker shall be posted
|