Permit Information
Permit NumberELE06-04033
StatusFinaled
Name ELCOR ELECTRIC
Site Address 4211 W FRANKLIN RD
Project Name 
Customer Number 
ePlanReview 
Description
Temporary Power Pole: temp pole
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Temporary Service11/8/200611/9/200611/9/2006APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corr made, t/s o/h n ok
Temporary Service10/31/200610/31/200610/31/2006PFAIL
DetailsBob Reichert
Temp pole; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken or cut parts- panel, recpt, 230.28 service mast shall be adequate strength to support conductors,230.26 point of attachment of service drop conductors shall be minimum 10' above grade, 110.12(A) unused openings shall be closed (bottom raceway), 110.3(B) only breakers shall be used per mfgrs listing and labelling, BCC job id sticker shall be posted