Final | 11/20/2006 | 11/21/2006 | 11/21/2006 | A | PASS |
Bob Reichert
|
|
|
shad ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final, signed card
|
Final | 11/17/2006 | 11/20/2006 | 11/20/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung told contr, left corr notice, nec 110.26(F)(1) there shall be no foreign piping over panel dedicated space, 330.30(B) mc cable shall be strapped within 12" of box,358.30(A) emt shall be secured every 10' and within 3' of box, 300.15 mc cable shall term in box,BCC no violations shall be retained
|
Final | 11/16/2006 | 11/16/2006 | 11/16/2006 | P | PART |
Bob Reichert
|
|
|
doug; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles elect shall fix subpanel grounding, provide drip protection, finish lighting over cash wrap, and sign ckt, will check flat type recpts in wiremold
|
Electrical Rough-In | 11/1/2006 | 11/2/2006 | 11/2/2006 | A | PASS |
Bob Reichert
|
|
|
Doug Moyle ###-#### ric walls only ok
|