Temporary Service | 11/3/2006 | 11/6/2006 | 11/6/2006 | A | PASS |
Bob Reichert
|
|
|
Re inspect temp pole; Phone #: ###-#### Internet Inspection Request from: todd hall corr made, t/s u/g n ok
|
Temporary Service | 11/2/2006 | 11/3/2006 | 11/3/2006 | A | FAIL |
Jack Frank
|
|
|
call AJ with any questions; Phone #: ###-#### Internet Inspection Request from: todd hall corr needs conn for GEC, needs inuse cover 240V recept, shall not use SS emt conn. for chase nipple, drive grd rod flush, clean dirt for t/s
|