Final | 3/8/2007 | 3/8/2007 | 3/8/2007 | P | PASS |
William E Thomas
|
|
|
fred ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
survey- 210.52
|
Permanent Service | 2/15/2007 | 2/16/2007 | 2/16/2007 | A | PASS |
William E Thomas
|
|
|
fred; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s o/h n ok
|
Permanent Service | 2/15/2007 | 2/15/2007 | 2/15/2007 | P | PASS |
William E Thomas
|
|
|
fred; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt p/s o/h n ok
|
Permanent Service | 2/13/2007 | 2/14/2007 | 2/14/2007 | A | FAIL |
Bob Reichert
|
|
|
fred ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr., left corr notice, nec 250.24(A) grounding electrode conductor shall be connected to grounded service conductor
|
Permanent Service | 1/22/2007 | 1/22/2007 | 1/22/2007 | P | FAIL |
William E Thomas
|
|
|
fred; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 1. not properly grounded 2. not properly bonded
|
Electrical Rough-In | 1/17/2007 | 1/17/2007 | 1/17/2007 | P | PASS |
Mike Kinnear
|
|
|
jeremy; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok cover concrete with dirt note call electrical contractor advised him the grounding was wrong he will fix & recall for perment service inspection
|
Electrical Rough-In | 1/10/2007 | 1/11/2007 | 1/11/2007 | A | PART |
Pat Lass
|
|
|
jeremy ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith electrode ok for concrete
|
Rough-In Permanent Service | 11/9/2006 | 11/9/2006 | 11/9/2006 | P | PART |
Pat Lass
|
|
|
fernando; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles service requires concrete encased electrode R/I Ok
|