Permit NumberELE06-04191
StatusFinaled
Name TEJANO HVAC & ELECTRIC
Site Address 3220 N 32ND ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/8/20073/8/20073/8/2007PPASS
DetailsWilliam E Thomas
fred ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith

survey- 210.52












Permanent Service2/15/20072/16/20072/16/2007APASS
DetailsWilliam E Thomas
fred; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
p/s o/h n ok
Permanent Service2/15/20072/15/20072/15/2007PPASS
DetailsWilliam E Thomas
fred; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt
p/s o/h n ok
Permanent Service2/13/20072/14/20072/14/2007AFAIL
DetailsBob Reichert
fred ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr., left corr notice, nec 250.24(A) grounding electrode conductor shall be connected to grounded service conductor
Permanent Service1/22/20071/22/20071/22/2007PFAIL
DetailsWilliam E Thomas
fred; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
1. not properly grounded
2. not properly bonded
Electrical Rough-In1/17/20071/17/20071/17/2007PPASS
DetailsMike Kinnear
jeremy; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok cover concrete with dirt note call electrical contractor advised him the grounding was wrong he will fix & recall for perment service inspection
Electrical Rough-In1/10/20071/11/20071/11/2007APART
DetailsPat Lass
jeremy ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
electrode ok for concrete
Rough-In Permanent Service11/9/200611/9/200611/9/2006PPART
DetailsPat Lass
fernando; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
service requires concrete encased electrode
R/I Ok