Final | 12/7/2006 | 12/8/2006 | 12/8/2006 | A | PASS |
Jack Frank
|
|
|
brandon - as early as possible ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok card signed
|
Electrical Rough-In | 12/7/2006 | 12/7/2006 | 12/7/2006 | P | PASS |
Jack Frank
|
|
|
brandon Note: ceiling ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Rough-In Permanent Service | 11/21/2006 | 11/21/2006 | 11/21/2006 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/21/2006 at 9:39:08 AM. no p/s r/i for all walls and hard ceilings ok
|
Electrical Rough-In | 11/16/2006 | 11/16/2006 | 11/16/2006 | P | PART |
Jack Frank
|
|
|
security wall only anop
|
Electrical Rough-In | 11/16/2006 | 11/16/2006 | 11/16/2006 | P | FAIL |
Jack Frank
|
|
|
wall cover; Phone #: ###-#### Internet Inspection Request from: Don Spackman called corr , 314.16 box fill handy boxes used at show window outlets, 300.11 raceway shall not support phone cable at panel, 300.4 nail plates and 11/4" parallel 358.30 and 330.30 secure raceways and cables within 3ft for emt 12" for MC, noted to general about bi level switching told him to contact structual inspector
|