Permanent Service | 1/3/2007 | 1/3/2007 | 1/3/2007 | P | PASS |
Pat Lass
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles P/S O/H N Ok
|
Electrical Rough-In | 12/5/2006 | 12/5/2006 | 12/5/2006 | P | PASS |
Jack Frank
|
|
|
mark ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith r/i ok
|
Rough-In Permanent Service | 12/1/2006 | 12/1/2006 | 12/1/2006 | P | FAIL |
Bob Reichert
|
|
|
mark ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, no answer, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 300.4(1) edge of bored holes shall be 1 1/4" from edge of framing members, 250.24(A)(4) grounding connection shall not be made to grounded conductor on load side of service disc
|