Final | 12/29/2006 | 1/2/2007 | 1/2/2007 | A | PASS |
Bob Reichert
|
|
|
Work performed by Ron Chaney.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz corr made, ok to final
|
Electrical Rough-In | 12/8/2006 | 12/13/2006 | 12/13/2006 | A | FAIL |
Bob Reichert
|
|
|
Work performed by Ron Chaney.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz called contr, nec 680.22(A)(3) recpt shall be minimum 10' from inside wall of tub, blank off recpt and relocate new one since exst trips kitchen gfci
|