Electrical Rough-In | 8/26/2007 | 8/27/2007 | 8/27/2007 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/26/2007 at 8:32:44 PM. Contact: ###-####. r/i ok
|
Electrical Rough-In | 8/20/2007 | 8/20/2007 | 8/20/2007 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/20/2007 at 6:44:30 AM. Contact: ###-####. corr. do not cover met owner, 314.16 box fill outside recept and jbox attic by closet door, 250.148 grd all metal boxes, 210.52(A) outlet spacing, 300.14 grd wires cut short , 110.14(B) all splices need a splicing means wires just twisted, note told owner to check manufactures instructions for location of smoke detector too close to vent?
|
Conference | 6/4/2007 | 6/6/2007 | 6/6/2007 | P | DONE |
Jack Frank
|
|
|
Barry ; Phone #: ###-#### Internet Inspection Request from: Darla Downs called owner, answered all questions explained NEC reqirements, he will request r/i when ready
|