Final | 2/2/2007 | 2/2/2007 | 2/2/2007 | P | PASS |
Mike Kinnear
|
|
|
reinspection Phone #: ###-#### ok final corrections made
|
Final | 2/1/2007 | 2/1/2007 | 2/1/2007 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### corrr. called 110.26(A)(1) table shall provide required clearences for panels, 406.4(A B D) recepts are loose in boxes and set back in plates, all locations
|
Final | 1/30/2007 | 1/31/2007 | 2/1/2007 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### called needs other elect. contr. to call for final or t/o for shell before final or t/o for tenant
|
Conference | 2/1/2007 | 2/1/2007 | 2/1/2007 | A | PASS |
Jim Schmer
|
|
|
conf. on why inspection was not done. Shell and core not t/o so could not do tenant space.
|
Electrical Rough-In | 1/29/2007 | 1/29/2007 | 1/29/2007 | P | PASS |
Jack Frank
|
|
|
ceiling inspection Phone #: ###-#### ceilings ok for high and low voltage
|
Electrical Rough-In | 1/26/2007 | 1/26/2007 | 1/26/2007 | P | FAIL |
Jack Frank
|
|
|
ceiling inspection. If any way it could be done in the morning it would be appreciated. Thank you Phone #: ###-#### corr. posted for high and low voltage, high V 110.12(A) seal all KOs, install covers all boxes, low V 800.21&24, 830.21&24 remove cables that lay on grid and support and secure, same for stat and other hvac wiring
|
Electrical Rough-In | 1/12/2007 | 1/12/2007 | 1/12/2007 | P | PASS |
William E Thomas
|
|
|
1. ri for front east front of building ok to cover.
|
Electrical Rough-In | 1/12/2007 | 1/12/2007 | 1/12/2007 | P | CANC |
William E Thomas
|
|
|
Rough in on walls, store front Phone #: ###-#### 1. no permit for core and shell electrical. 2. 517.78 grounding of xray equipment 3. 110.3 labeling and listing of xray equipment.
|
Electrical Rough-In | 12/14/2006 | 12/14/2006 | 12/14/2006 | P | PART |
Jack Frank
|
|
|
rough in on walls; Phone #: ###-#### Internet Inspection Request from: DJ Carman walls
|