Final | 4/27/2007 | 4/30/2007 | 4/30/2007 | A | PASS |
Bob Reichert
|
|
|
Jeff; Phone #: ###-#### Internet Inspection Request from: Andrea Whiteman ok to final
|
Final | 4/12/2007 | 4/13/2007 | 4/13/2007 | A | CANC |
Bob Reichert
|
|
|
Jeff; Phone #: ###-#### Internet Inspection Request from: Stacie Backus elect did not call for insp here, contact notes not affiliated with this job
|
Electrical Rough-In | 12/21/2006 | 12/22/2006 | 12/22/2006 | A | PASS |
Bob Reichert
|
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
|
Electrical Rough-In | 12/19/2006 | 12/20/2006 | 12/20/2006 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/19/2006 at 1:00:15 PM. Contact: ###-####. called left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 314.17(C) nm cable shall be stapled within 8" of box, 314.23 boxes shall be securely fastened, 110.12(C) casble shall not be damaged by tub, BCC all make-up shall be done
|
Electrical Rough-In | 12/18/2006 | 12/19/2006 | 12/19/2006 | A | NH |
Bob Reichert
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left card
|