Final | 6/25/2008 | 6/26/2008 | 6/26/2008 | A | PASS |
Bob Reichert
|
|
|
boun Phone #: ###-#### corrections made, ok to final
|
Final | 6/13/2008 | 6/19/2008 | 6/19/2008 | P | FAIL |
Bob Reichert
|
|
|
Boun Phone #: ###-#### met owner, told to provide 18"x24" access hatch for tub per mfgr's instruction, label panels, provide abrasion protection for gec at meter, u/g ok for grounding electrode, rest ok
|
Final | 6/12/2008 | 6/13/2008 | 6/13/2008 | P | CANC |
Bob Reichert
|
|
|
boun Phone #: ###-#### Inspection cancelled from web by: Alexandra Rahn
|
Permanent Service | 11/19/2007 | 11/20/2007 | 11/20/2007 | A | PASS |
William E Thomas
|
|
|
larry - please call 1/2 hr prior to inspection Phone #: ###-#### . 1. p/s u/g reconnect ok. .
|
Permanent Service | 11/19/2007 | 11/19/2007 | 11/19/2007 | P | FAIL |
Bob Reichert
|
|
|
Larry Sanders (Dad) ###-#### //please call 30 min prior, needs to be there because 2 large dogs in yard met owner, left corr notice, nec 110.36 shall provide clearances in frontof electrical equipment in and out, 312.6 conductors shall not be deflected more than table allows, 250.52 shall provide grounding electrodes, Chapter 9 shall not overfill conduit, anote- shall make line and load at meter correct
|
Electrical Rough-In | 3/26/2007 | 3/28/2007 | 3/28/2007 | A | PASS |
Bob Reichert
|
|
|
Boun; Phone #: ###-#### Internet Inspection Request from: Stacie Backus met owner, ric ok, tub ok
|
Conference | 12/20/2006 | 12/21/2006 | 12/21/2006 | A | DONE |
Bob Reichert
|
|
|
bounthavy - ###-#### cell talked about basic wiring for addition, check room count at ri
|